20381
Accession Number
26045
Author
Padfield, Tim; Jensen, Poul
Editor
Grimstad, Kirsten
Title Of Article Chaper
Low energy climate control in museum stores
Title Of Journal Book
ICOM Committee for Conservation, 9th triennial meeting, Dresden, German Democratic Republic, 26-31 August 1990: preprints
Pages
596-601
Collation
4 figs.
Reference Bibliography
7 refs.
Publisher
ICOM Committee for Conservation
Publisher City
Paris
ISBN
0-89236-185-9
Language Of Text
English
Language Of Summary
English
Literature Type
Monograph : Proceedings
Literature Level
Analytic
Meeting
ICOM Committee for Conservation. Meeting
Abstract
A computer model of a museum store is used to explore the effects of various methods of air conditioning. A room that is filled with an abundance of hygroscopic material can be held at a constant relative humidity by blowing in a stream of air, about one twentieth of the room volume per hour, which has a water content adjusted to be in equilibrium with the desired water content in the hygroscopic materials. This method works even if the temperature is uncontrolled, because of the buffer effect. The room also needs air recirculation at about one change per hour to ensure temperature uniformity and to allow the removal by filtration of internally generated pollutants.
Keywords
museum store; computers; modeling; air conditioning; environmental control; relative humidity; temperature; pollutants
pub_id
20381