19852
Accession Number
29549
Author
Padfield, Tim
Author Affiliation
The National Museum of Denmark. Conservation Department
Title Of Article Chaper
Low-energy climate control in museum stores: a postscript
Title Of Journal Book
ICOM committee for conservation, 11th triennial meeting in Edinburgh, Scotland, 1-6 September 1996: Preprints
Pages
68-71
Reference Bibliography
3 bibliog. refs.
Publisher
James & James (Science Publishers) Ltd.
Publisher City
London
ISBN
1-873956-50-8
Language Of Text
English
Language Of Summary
English
Literature Type
Monograph : Proceedings
Literature Level
Analytic
Meeting
ICOM Committee for Conservation triennial meeting (11)
Meeting Country
United Kingdom
Abstract
A large museum storage building whose relative humidity was controlled by warming to reduce relative humidity showed a violently oscillating tempoerature which a period of about a week, as predicted by a computer model. The principle of humidity control by heating a building when the RH drops below the set point does not work in buildings that have a small air exchange rate and are filled with water absorbent materials. Such buildings must be controlled by dehumidification or by heating at constant energy input. -- ICCROM
Keywords
Museum; Storage; Environment; Control; Climatology; Interior; Relativ e humidity -- ICCROM
pub_id
19852
Meeting Date
19960901-19960906